Tel/Whatsapp/Wechat : 13631609858
E-mail : sales@smartlightdesigner.com
Nov 2021
Direct push method:
1. It is required to provide LM-84 reports of bulbs and lamps. The test cycle is 6000 hours, and the test interval should not exceed 1000 hours.
2. The derivation formula is the same as TM-21. The temperature insertion method can also be used (then LM-84 is required to be done at multiple temperatures).
3. No LM-80 report is required.
4. The requirements for the number of samples and the upper limit of the estimated period are as follows, and the coefficient x is a multiple of the total test period that can be estimated.
Number of samples |
Coefficient X |
3 | 3 |
4 | 4 |
5-6 | 5 |
7-9 | 5.5 |
≥ 10
|
6 |
For example, if 3 samples are tested for 6000 hours, the estimated upper limit is 18000 hours.
If you compare the lamp standard requirements of ENERGY STAR®: without LM-80 report, the lamp only needs to be tested for 0 hours
And 6000 hours of aging time (life upgrade is calculated separately, the test cycle is 1/4 of the declared life). Then the required test interval for TM-28
It is 1000 hours, which increases the test time point, but if it is estimated that 4 times the test period, only 4 samples are needed, which is less than ENERGY STAR
The number of samples.
4. The requirements for the number of samples and the upper limit of the estimated period are as follows, and the coefficient x is a multiple of the total period of IES LM-84 that can be estimated. .
Number of samples |
Coefficient X |
5 | 1.5 |
6 | 2 |
7 | 2.5 |
8 | 3 |
9 | 3.5 |
10 | 4 |
11 | 4.5 |
12 | 5 |
13-14 | 5.5 |
≥15
|
6 |
For example, if 10 samples are tested for 3000 hours, the upper limit of the estimated period shall not exceed 12000 hours.
If you compare the lamp standard requirements of ENERGY STAR®: with the LM-80 report, the china led outdoor lamp only needs to be tested for 0 hours
And 3000 hours, it can be estimated to 25000 hours. If calculated according to LM-84, even if 15 samples are used, after 3000 hours
It can only be estimated to 18,000 hours, which can barely meet the minimum life requirements of decorative lights. To meet the 25,000 hour requirement, you must
If more than 12 samples are used for more than 5000 hours of testing, then the combination calculation is meaningless. Because if you don’t care too much at this time
For 1000 hours, we can completely choose to use the direct push method after 6000 hours of testing, so that the test interval can be extended to 1000
Hours to reduce the test burden.
In summary, if the current requirements of the Energy Star bulb standard are compared, the calculation method not only fails to reduce the test burden, but greatly increases
Increased the burden of testing. However, this does not deny the rationality of this standard. The possibility of the standard being adopted still exists.
At the burden of the manufacturer, the certification body may make appropriate adjustments to the test requirements or calculation requirements.